Trystan Lea

Room by room heat loss calculation

Published: 29th December, 2017

Updated: July 2024

The first step in designing any heat pump system is to perform a heat loss calculation. This calculation estimates the amount of heat a house needs to reach a target internal temperature when it is very cold outside. It is also used to size radiators or underfloor heating to ensure that each room receives the appropriate amount of heat.

The results of a heat loss calculation are only as good as the assumptions that go into it. While it is relatively easy to accurately measure room dimensions, other assumptions, such as air change rates and fabric U-values, are more challenging to get right. The current CIBSE guidance for pre-2000 air change rates, in particular, results in widespread overestimates of building heat loss and, consequently, oversizing of the resulting heating system.

There are a large number of good heat loss calculation tools. One of the easiest free tools is https://heatpunk.co.uk by Midsummer. I have also developed my own open source tool called HeatLoss.js and while it has some advanced features, it is certainly harder to enter in all the building dimensions.

Left: HeatPunk by Midsummer. Right: HeatLoss.js by OpenEnergyMonitor.

heatpunk_heatlossjs.png

Heat Loss Calculation Steps:

1. What is the house made of? Tools typically start by defining a list of the materials and associated U-values for the different building elements: external walls, internal walls, ground floor, intermediate floors, loft/roof, windows, and doors. MCS provides a guidance document on U-values, which offers a useful starting point; see: Guidance on U-values from Domestic Heating Design Guide. It is worthwhile to search for the latest research on U-values, as the design guide is not always realistic or up-to-date. A good example is the research by SPAB on real-world U-values of solid stone walls, which suggests typical U-values closer to 1.5 W/K.m² for 500mm thick walls. I have used this value in my updated heat loss calculations included below.

2. Draw a plan of the house. Measure all the room, window, and door dimensions. With Heatpunk, you can draw the house using the 2D design tool on the fly. While it is good to be as accurate as possible, it does not have to be perfect, as the errors introduced by other assumptions are much greater than those likely to be caused by minor inaccuracies in the plan. For that matter, the calculation method itself and the convention of using internal dimensions without fully accounting for internal wall widths and corner details will introduce more significant sources of error than being off by a few centimeters. It can make sense to simplify and rationalize the plan so that dimensions line up between floors to make entry easier.

3. Select room temperatures. For non-MCS installations, you can choose the internal temperatures to match your comfort preferences. For an MCS installation, the MIS_3005 MCS design standard states that the system "should" use internal temperatures not less than those specified in Table 1. The term "should" indicates a prescribed "requirement or procedure that is intended to be complied with unless reasonable justification can be given." This suggests there could be some flexibility for selecting lower temperatures (e.g., in the bathroom), but what might pass for "reasonable justification" is not described in any further detail in the document.

Here are the relevant tables from the MCS MIS_3005 standard document and the CIBSE Domestic Heating Guide for reference:

internal_temperatures.png

The average internal temperature resulting from the range of standard MCS room temperatures in a typical domestic property is less stringent than assuming a uniform internal design temperature of 20°C throughout (e.g., Passivhaus requirement). In my mid-terrace house, setting 21°C in the living room, 22°C in the bathroom, and 18°C everywhere else results in an average internal temperature of 19.3°C.

The most challenging room temperature target for system design is often the bathroom temperature target of 22°C. Our bathroom's assessed heat loss is relatively high due to its two external walls, and the space for a large radiator was limited, leading to an undersized bathroom radiator. However, the temperature has worked out just fine in reality, typically around 19-20°C when in use, which feels comfortable enough. The bathroom gains some heat from the hot water cylinder and heat pump pipework, which are not usually included in simple heat loss calculations. It is also partly heated by warm air moving up from the larger radiator in the hall.

For our heat loss calculation, I deviated slightly from the CIBSE guidance and targeted 20°C in the living room and 19°C everywhere else. This results in the same overall average temperature of 19.3°C but with a slightly different distribution: warmer bedrooms, hall, and landing, and a cooler bathroom.

4. Select Room Air Change Rates.

This is one of the most important, yet often overlooked, factor in heat loss calculations. As mentioned above, the current CIBSE guidance for pre-2000 air change rates suggests values significantly higher than those likely in reality, resulting in widespread overestimates of building heat loss.

To give an example for our mid-terrace house:

The blower door and CO2 monitoring results suggest that a whole house air change rate of around 0.6 ± 0.2 ACH is typical for our house. This value coincidentally matches the Part F building regulations' minimum whole dwelling ventilation rate (Table 1.3), which also works out to 0.6 ACH for our house. See the section on Part F building regulations.

I have used 0.6 ACH for all rooms in my heat loss calculation examples below. This reduces overall heat loss from ventilation by approximately 1.5 kW compared to assuming default pre-2000 CIBSE values.

5. Select a Suitable Design Outside Temperature.

The MCS design standard states that the heat loss calculation "should be performed .. using external temperatures specified in Table 2 colum A or B, according to the MCS Contractor's assessment of the building location. If column B is selected no uplift factor for intermittent heating is required.". The term should again means that alternative values are allowed provided reasonable justification can be given.

We can see from this table that the suggested design temperature varies significantly across the country:

The heatpunk tool suggests a design temperature of -3.6°C for my location. I have typically used -3°C from Table 3.7 of the CIBSE domestic heating guide. There is a good case for a higher design temperature in our particular location. Analysing temperature data from our outside temperature sensor with 5 years of data suggests a design temperature of -1.1°C (99.6%) and 0.0°C (99%). Met office data for the local village over the last year suggests -1.4°C (99.6%) and -0.1°C (99%). There are further results and example code for calculation documented here.

6. Ground Temperatures and Heated or Unheated Neighbours?

MCS state that the average external air temperature is to be used for the ground temperature on the other side of a solid floor. The nearest location in the MGD 007 Section 5 table page 44 suggests 10.0°C. Met office data for our nearest village suggests 10.6°C.

The CIBSE Domestic heating guide states that adjoining properties should be treated as unheated spaces to ensure that the heating system has enough capacity even when the adjoining property is unoccupied. An unheated temperature corresponding to the average external air temperature is suggested (e.g 10°C).

In our mid-terrace case, both neighbours are occupied and heated. Setting the neighbouring temperature to 18°C produces a heat loss value that more closely matches measured heat demand around 3.3 kW. If both neighbours are unheated this would increase to 4.2 kW.

Example Calculations:

The following example heat loss calculations in both Heatpunk and Heatloss.js use the key modifications to standard input assumptions discussed above, including:

Heat loss calculations:

Typical vs Worst Case Conditions

Some over-sizing of the heat pump compared to the accurate typical heat loss of 3.3 kW is fine. We have a 5 kW Ecodan that can reliably deliver up to 4.2-4.5 kW during heavy defrost conditions. This 1.27x to 1.36x over-sizing factor based on an accurate heat loss gives us some margin to cover at least some of these worst-case conditions.

It's Easy to Over-Inflate Heat Loss!

If we start with our base heat loss of 3340W from the HeatLoss.js example and change the key input assumptions to use standard values:

It is quite normal for heat loss calculations to be done using these standard values, which unfortunately leads to significant system over-sizing. Further over-sizing factors are often added on top of these inflated heat loss results as you choose the next heat pump size up. I made most of these errors myself when I did my first heat loss calculation for the house in 2017, coming up with a heat loss of 6 kW. I luckily chose to undersize the heat pump, thinking I might need to top up using the wood stove, but this turned out not to be necessary. The next heat pump up in the Ecodan range was 8.5 kW, which would have resulted in an over-sizing factor of 2.5x!

A Note on Hot Water Demand and Heat Gains

To keep calculations simple, most heat loss calculations do not account for the additional heat required for hot water demand and do not subtract heat gains such as solar gains, body heat, and heat given off by running electrical appliances. Coincidentally, these factors seem to mostly cancel out in our house.

On the coldest days, the heat demand for hot water can be 11 kWh/day, equivalent to a continuous 460W. Heat gains from body heat may be around 140W, from electrical appliances about 240W, and from heat lost from the hot water system around 105W (approximately 25% of hot water demand). Solar gains may be as low as 30-40W.

We can therefore add 460W (hot water demand) minus 115W (heat gains) = 345W of net heat demand for hot water. Then, subtracting the heat gains from body heat (140W), electrical appliances (240W), and solar gains (40W) results in -75W.

This net effect of -75W is really within the range of rounding errors in a heat loss calculation. We can therefore expect that the maximum heat demand measured by the heat pump heat meter should match the calculated heat loss value.

The maximum heat output required from the heat emitters is of course affected by these gains and will be about 0.4 kW less than the overall heat loss or heat demand figure. E.g 3.3 kW - 0.4 kW gains = 2.9 kW in our case. The heat pump still needs to cater for the 3.3 kW as this includes hot water.

Comparison with Monitored Heat Demand

I have now had my heat pump running with detailed monitoring for five and a half years, allowing me to check the actual maximum heat demand that the heat pump has provided.

See HeatpumpMonitor.org heat demand tool here: https://heatpumpmonitor.org/heatloss?id=2

midterrace_measured_heat_demand.png

Results:

Choosing the right Design Flow Temperature

Heat pump radiator systems are usually designed to operate at a design flow temperature of 45-50°C at the chosen design outside temperature, for example, -3°C. However, due to commonly overestimated heat loss calculations, the actual required design flow temperature or weather compensation curve setting is often much lower than the calculated design flow temperature. Systems that have had their weather compensation settings tuned after installation can often achieve higher SCOP performance results than initially expected.

To illustrate this with our house:

  1. The radiator system I designed for our house would need to run at a design flow temperature of 50°C at the design outside temperature to deliver the overestimated heat loss of 7.5 kW (-0.4 W gains = 7.1 kW delivered by the radiators). On paper, one might think that this design flow temperature is quite high and not conducive to cheap running costs. Using the SCOP calculator here, I estimate that my SCOP would have been 3.46 at this higher design flow temperature.

  2. With our actual heat loss of 3.3 kW (2.9 kW delivered by the radiators), with all of the more accurate input assumptions above, this same radiator system only needs a design flow temperature of 35°C. This actual setting has provided me with a space heating SCOP of 4.2-4.3. This SCOP would be even higher with the latest generation of heat pumps, possibly reaching 4.7.

  3. Had I initially calculated an accurate heat loss of 3.3 kW (2.9 kW delivered by the radiators), I could have used the original single panel radiator system at a design flow temperature of 47°C. The performance of the system would have been lower, with a space heating SCOP of approximately 3.4.

Important: If we start conducting accurate heat loss assessments but do not reconsider the general design flow temperature rule of thumb of 45-50°C, any performance gain from a better-matched heat pump will likely be undone by higher running flow temperatures.

The average monitored design flow temperature of 8 systems with a space heating SCOP of 4 or above on HeatpumpMonitor.org is ~36°C, these systems have an average SCOP of 4.4. There is one system with a SCOP of 4.2 with a design flow temperature of 40°C.

This suggests that for space heating SCOPs of more than 4.0 with an *accurate heat loss*, choose a design flow temperature of no higher than 40°C.